Cable length [m (ft)]
AC line voltage [V]
Rise time [μsec]
V
peak
[kV]
dU/dt [kV/μsec]
50 (164)
400
0.222
1.00
3.603
400 V 22 kW (30 hp)
5 (16)
400
0.132
0.88
5.220
25 (82)
400
0.172
1.026
4.772
50 (164)
400
0.222
1.00
3.603
400 V 30 kW (40 hp)
10 (33)
400
0.376
0.92
1.957
50 (164)
400
0.536
0.97
1.448
100 (328)
400
0.696
0.95
1.092
150 (492)
400
0.8
0.965
0.965
10 (33)
480
0.384
1.2
2.5
50 (164)
480
0.632
1.18
1.494
100 (328)
480
0.712
1.2
1.348
150 (492)
480
0.832
1.17
1.125
10 (33)
500
0.408
1.24
2.431
50 (164)
500
0.592
1.29
1.743
100 (328)
500
0.656
1.28
1.561
150 (492)
500
0.84
1.26
1.2