fsw[kHz]
20 10
0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
110%
I
out[%]
16
40
45
50
5
o
C
o
C
o
C
e30bh858.10
Illustration 21: 400 V IP20 H4 10 kW (15 hp)
fsw[kHz]
20 10
0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
110%
I
out
[%]
16
40
45
50
5
o
C
o
C
o
C
e30bh859.10
Illustration 22: 200 V IP20 H5 10 kW (15 hp)
5.3.5.2 Derating Curves, 18.5–22 kW
Drives in the power range 18.5–22 kW are able to deliver 100% current in ambient temperatures up to 52 °C (125 °F) with a default
switching frequency of 5.0 kHz (f_sw). If the switching frequency is increased, the following derating curves apply.
e30bi924.10
0
10
%
20
%
30
%
40
%
50
%
60
%
70
%
80
%
90
%
100
%
110
%
0
2
5
10 16
52 °C
45 °C
40 °C
I
out
[%]
f
sw
[
kHz
]
Illustration 23: 400 V IP20 H5 18.5–22 kW (25–30 hp)
5.3.5.3 Derating Curves, 30 kW
Drives in the power range 30 kW are able to deliver 100% current in ambient temperatures up to 45 °C (113 °F) with a default
switching frequency of 4.0 kHz (f_sw). If the switching frequency is increased, the following derating curves apply.
AJ330233902305en-000201 / 130R059640 | Danfoss A/S © 2021.05
Mechanical Installation
Considerations
VLT® Compressor Drive CDS 803
Design Guide

Table of Contents

Other manuals for Danfoss VLT CDS 803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 803 and is the answer not in the manual?

Danfoss VLT CDS 803 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 803
CategoryDC Drives
LanguageEnglish

Related product manuals