EasyManua.ls Logo

Danfoss VLT CDS 803 - IP21;NEMA Type 1 Enclosure Kit

Danfoss VLT CDS 803
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
e30bi925.10
0
10%
20%
30%
40%
50%
60%
70%
80%
90%
100 %
110 %
0
2
4
10
6
50 °C
45 °C
40 °C
I
out
[%]
f
sw
[
kHz
]
8
12
Illustration 24: 400 V IP20 H6 30 kW (40 hp)
5.3.6 Derating for Low Air Pressure and High Altitudes
The cooling capability of air is decreased at low air pressure. For altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV.
Below 1000 m (3281 ft) altitude, derating is not necessary. For altitudes above 1000 m (3281 ft), decrease the ambient temperature
or the maximum output current. Decrease the output by 1% per 100 m (328 ft) altitude above 1000 m (3281 ft) or reduce the maxi-
mum ambient cooling air temperature by 1 °C (1.8 °F) per 200 m (656 ft).
5.4 IP21/NEMA Type 1 Enclosure Kit
If environment, air quality, or surroundings require extra protection, an IP21/NEMA Type 1 kit can be ordered, see 7.3 Accessories
and Spare Parts. The IP21/NEMA Type 1 is an optional enclosure element available for IP20 units. If the enclosure kit is used, an IP20
unit is upgraded to comply with enclosure IP21/NEMA Type 1.
N O T I C E
The IP21/IP21 are not suitable for outdoor mounting.
AJ330233902305en-000201 / 130R0596 | 41Danfoss A/S © 2021.05
Mechanical Installation
Considerations
VLT® Compressor Drive CDS 803
Design Guide

Table of Contents

Other manuals for Danfoss VLT CDS 803

Related product manuals