3.2. Configure the Master
3.2.1. EDS File
A large part area of the system configuration is the setting of application related parameters. EDS
(Electronic Data Sheet) files simplify the setting up of most of the DeviceNet configurable param-
eters. Danfoss provides a generic English EDS file covering all voltage and power sizes, for off-
line configuration. The EDS file can be downloaded from http://www.danfoss.com/drives.
NB!
The EDS-file does not contain all parameters but a selected, limited number of pa-
rameters with generic minimum, maximum and default values.
3.3. Configure the Frequency Converter
3.3.1. VLT Parameters
Pay particular attention to the following parameters when configuring the frequency converter
with a DeviceNet interface. Please refer to the Parameters chapter for more details of each pa-
rameter.
Par. 0-40
[Hand on] key on LCP
.
If the Hand button on the frequency converter is activated, control of the drive via the
DeviceNet interface is disabled. After initial power-up the frequency converter will auto-
matically detect whether a fieldbus option is installed in slot A, and set par. 8-02
Control
Word Source
to [Option A]. If an option is added to, changed in or removed from an
already commissioned drive, it will not change par. 8-02 but will enter Trip Mode, and
the frequency converterwill display an error.
•Par. 8-10
Control Word Profile
(see section
How to Control the Frequency Converter
).
Choose between the Danfoss FC Profile and the ODVA profile. Select the desired Devi-
ceNet instance in par. 10-10
Process Data Type Selection
.
Par. 8-50 to 8-56 (see section
Parameters
). Selection of how to gate the DeviceNet con-
trol commands with digital input command of the control card.
Par. 8-03 to 8-05. The reaction in the event of a bus time out is set via these parameters
Par.. 10-01
Baud rate
. Default is 125 kbps.
Par. 10-02
MAC ID
. Default is 63.
3.3.2. LEDs
The DeviceNet control card contains two bi-colour (green/red) LEDs for each connector hook-up
port, to indicate the state of the device and the network respectively. For details of the range of
communications status indicated by the LEDs, please refer to the Troubleshooting chapter.
FC 100/ 200/ 300 DeviceNet 3. How to Configure the System
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
21
3

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals