Table 80: Wiring Configuration for Analog Voltage Feedback Transducer (4-wire)
Parameters
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
A54
U - I
0-10 V
+
-
e30bu080.10
XD2.10
XD2.11
XD2.12
XD2.13
XD2.18
XD2.14
XD2.15
XD2.16
XD2.17
XD2.19
XD2.6
XD2.7
XD2.8
XD2.9
XD2.5
XD2.4
Function
Setting
Parameter 6-20 Terminal 54 Low Voltage
0.07 V*
Parameter 6-21 Terminal 54 High Voltage
10 V*
Parameter 6-24 Terminal 54 Low Ref./Feedb. value
0*
Parameter 6-25 Terminal 54 High Ref./Feedb. Value
50*
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 54 in the parameter title corresponds to terminal XD2.8 in the control compartment.
8.1.5 Wiring Configuration: Run/Stop
Table 81: Wiring Configuration for Run/Stop Command with External Interlock
Parameters
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
e30bu081.10
XD2.10
XD2.11
XD2.12
XD2.13
XD2.18
XD2.14
XD2.15
XD2.16
XD2.17
XD2.19
Function
Setting
Parameter 5-10 Terminal 18 Digital Input
[8] Start*
Parameter 5-12 Terminal 27 Digital Input
[7] External interlock
*=Default value
Notes/comments:
D IN 37 is an option.
Terminal 18 in the parameter title corresponds to terminal XD2.12 in the control compartment.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.