9.2 Line Power Supply (3-phase)
Line power supply (L1, L2, L3)
Supply terminals L1, L2, L3
Supply voltage 380–480 V: -15% (-25%)
1)
to +10%
1) The adjustable frequency drive can run at -25% input voltage with reduced performance. The maximum output power of the
adjustable frequency drive is 75% if input voltage is -25% and 85% if input voltage is -15%.
Full torque cannot be expected at AC line voltage lower than 10% below the lowest rated supply voltage of the adjustable
frequency drive.
Supply frequency 50/60 Hz ±5%
Maximum imbalance temporary between line phases 3.0% of rated supply voltage
True power factor (λ) ≥0.9 nominal at rated load
Displacement power factor (cos ϕ) near unity (>0.98)
Switching on input supply L1, L2, L3 (power-ups) ≤7.5 kW (10 hp) Maximum two times/minute
Switching on input supply L1, L2, L3 (power-ups) 11–22 kW (15–30 hp) Maximum one time/minute
The unit is suitable for use on a circuit capable of delivering less than 5000 RMS symmetrical Amperes, 480 V maximum.
9.3 Motor Output and Motor Data
Motor output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency 0–500 Hz
Output frequency in VVC
+
Mode 0–200 Hz
Switching on output Unlimited
Ramp time 0.05–3600 s
Torque characteristics
Starting torque (constant torque) Maximum 160% for 60 s
1)
Overload torque (constant torque) Maximum 160% for 60 s
1)
Starting torque (variable torque) Maximum 110% for 60 s
1)
Overload torque (variable torque) Maximum 110% for 60 s
Starting current Maximum 200% for 1 s
Torque rise time in VVC
+
(independent of f
sw
) Maximum 50 ms
1) Percentage relates to the nominal torque.
9.4 Ambient Conditions
Ambient Conditions
IP class IP20
Vibration test, all enclosure sizes 1.0 g
Relative humidity 5–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Ambient temperature (at DPWM switching mode)
- with derating maximum 55°C (131 °F)
1)
- at full continuous output current with some power size maximum 50 °C (122 °F)
- at full continuous output current maximum 45 °C (113 °F)
Minimum ambient temperature during full-scale operation 0 °C (32 °F)
Minimum ambient temperature at reduced performance -10 °C (14 °F)
Temperature during storage/transport -25 to +65/70 °C (-13 to + 149/158 °F)
Maximum altitude above sea level without derating 1000 m (3300 ft)
Maximum altitude above sea level with derating 3000 m (10000 ft)
EMC standards, emission EN 61800-3, EN 61000-3-2, EN 61000-3-3, EN 61000-3-11,
Specications
VLT
®
Midi Drive FC 280
50 Danfoss A/S © 11/2015 All rights reserved. MG07A122