[0] >Ran3<
[1] >Ran5<
[2] >2.0 kHz<
[3] >3.0 kHz<
[4] >4.0 kHz<
*[5] >5.0 kHz<
[6] >6.0 kHz<
[7] >8.0 kHz<
[8] >10.0 kHz<
[9] >12.0kHz<
[10] >16.0kHz<
14-03 Overmodulation
[0] >O<
*[1] >On<
14-07 Dead Time Compensation Level
14-08 Damping Gain Factor
14-09 Dead Time Bias Current Level
14-1* Mains On/O
14-10 Mains Failure
*[0] >No function<
[1] >Ctrl. ramp-down<
[2] >Ctrl. ramp-down, trip<
[3] >Coasting<
[4] >Kinetic back-up<
[5] >Kinetic back-up, trip<
[6] >Alarm<
[7] >Kin. back-up, trip w recovery<
14-11 Mains Voltage at Mains Fault
14-12 Function at Mains Imbalance
*[0] >Trip<
[1] >Warning<
[2] >Disabled<
[3] >Derate<
14-15 Kin. Backup Trip Recovery Level
14-2* Reset Functions
14-20 Reset Mode
*[0] >Manual reset<
[1] >Automatic reset x 1<
[2] >Automatic reset x 2<
[3] >Automatic reset x 3<
[4] >Automatic reset x 4<
[5] >Automatic reset x 5<
[6] >Automatic reset x 6<
[7] >Automatic reset x 7<
[8] >Automatic reset x 8<
[9] >Automatic reset x 9<
[10] >Automatic reset x 10<
[11] >Automatic reset x 15<
[12] >Automatic reset x 20<
[13] >Innite auto reset<
[14] >Reset at power-up<
14-21 Automatic Restart Time
>0-600 s< *10 s
14-22 Operation Mode
*[0] >Normal operation<
[2] >Initialisation<
14-24 Trip Delay at Current Limit
14-25 Trip Delay at Torque Limit
14-27 Action At Inverter Fault
[0] >Trip<
*[1] >Warning or trip after warning<
14-28 Production Settings
14-29 Service Code
14-3* Current Limit Ctrl.
14-30 Current Lim Ctrl, Proportional Gain
14-31 Current Lim Ctrl, Integration Time
14-32 Current Lim Ctrl, Filter Time
14-4* Energy Optimising
14-40 VT Level
14-41 AEO Minimum Magnetisation
>40-75%< *66%
14-44 d-axis current optimization for IPM
14-5* Environment
14-50 RFI Filter
14-51 DC-Link Voltage Compensation
14-52 Fan Control
*[5] >Constant-on mode<
[6] >Constant-o mode<
[7] >On-when-Inverter-is-on-else-o
Mode<
[8] >Variable-speed mode<
14-55 Output Filter
14-6* Auto Derate
14-61 Function at Inverter Overload
14-63 Min Switch Frequency
*[2] >2.0 kHz<
[3] >3.0 kHz<
[4] >4.0 kHz<
[5] >5.0 kHz<
[6] >6.0 kHz<
[7] >8.0 kHz<
[8] >10.0 kHz<
[9] >12.0 kHz<
[10] >16.0 kHz<
14-64 Dead Time Compensation Zero
Current Level
14-65 Speed Derate Dead Time Compen-
sation
14-8* Options
14-89 Option Detection
14-9* Fault Settings
14-90 Fault Level
15-** Drive Information
15-61 Option SW Version
15-62 Option Ordering No
15-70 Option in Slot A
15-71 Slot A Option SW Version
15-0* Operating Data
15-00 Operating hours
15-01 Running Hours
15-02 kWh Counter
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
15-06 Reset kWh Counter
15-07 Reset Running Hours Counter
15-3* Alarm Log
15-30 Alarm Log: Error Code
15-31 InternalFaultReason
15-4* Drive Identication
15-40 FC Type
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-44 Ordered TypeCode
15-45 Actual Typecode String
15-46 Drive Ordering No
15-48 LCP Id No
15-49 SW ID Control Card
15-50 SW ID Power Card
15-51 Drive Serial Number
15-53 Power Card Serial Number
15-6* Option Ident
15-60 Option Mounted
15-9* Parameter Info
15-92 Dened Parameters
15-97 Application Type
15-98 Drive Identication
15-99 Parameter Metadata
16-** Data Readouts
16-0* General Status
16-00 Control Word
16-01 Reference [Unit]
16-02 Reference [%]
16-03 Status Word
16-05 Main Actual Value [%]
16-09 Custom Readout
16-1* Motor Status
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage
16-13 Frequency
16-14 Motor current
16-15 Frequency [%]
16-16 Torque [Nm]
16-18 Motor Thermal
16-20 Motor Angle
16-22 Torque [%]
16-3* Drive Status
16-30 DC Link Voltage
16-33 Brake Energy /2 min
16-34 Heatsink Temp.
16-35 Inverter Thermal
16-36 Inv. Nom. Current
16-37 Inv. Max. Current
16-38 SL Controller State
16-39 Control Card Temp.
16-5* Ref. & Feedb.
16-50 External Reference
16-52 Feedback[Unit]
16-53 Digi Pot Reference
16-57 Feedback [RPM]
16-6* Inputs & Outputs
16-60 Digital Input
16-61 Terminal 53 Setting
16-62 Analog Input 53
16-63 Terminal 54 Setting
16-64 Analog Input AI54
16-65 Analog Output 42 [mA]
16-66 Digital Output
16-67 Pulse Input 29[Hz]
16-68 Pulse Input 33 [Hz]
16-69 Pulse Output 27 [Hz]
16-71 Relay Output
16-72 Counter A
16-73 Counter B
16-74 Prec. Stop Counter
16-8* Fieldbus & FC Port
16-80 Fieldbus CTW 1
16-82 Fieldbus REF 1
16-84 Comm. Option STW
16-85 FC Port CTW 1
16-86 FC Port REF 1
16-9* Diagnosis Readouts
16-90 Alarm Word
16-91 Alarm Word 2
16-92 Warning Word
16-93 Warning Word 2
16-94 Ext. Status Word
16-95 Ext. Status Word 2
16-97 Alarm Word 3
18-** Data Readouts 2
18-9* PID Readouts
18-90 Process PID Error
18-91 Process PID Output
18-92 Process PID Clamped Output
18-93 Process PID Gain Scaled Output
21-** Ext. Closed Loop
21-1* Ext. CL 1 Ref./Fb.
21-11 Ext. 1 Minimum Reference
21-12 Ext. 1 Maximum Reference
21-13 Ext. 1 Reference Source
21-14 Ext. 1 Feedback Source
21-15 Ext. 1 Setpoint
21-17 Ext. 1 Reference [Unit]
21-18 Ext. 1 Feedback [Unit]
21-19 Ext. 1 Output [%]
21-20 Ext. 1 Normal/Inverse Control
21-21 Ext. 1 Proportional Gain
21-22 Ext. 1 Integral Time
21-23 Ext. 1 Dierentation Time
21-24 Ext. 1 Dif. Gain Limit
22-** Appl. Functions
22-4* Sleep Mode
22-40 Minimum Run Time
22-41 Minimum Sleep Time
22-43 Wake-Up Speed [Hz]
22-44 Wake-Up Ref./FB Di
22-45 Setpoint Boost
22-46 Maximum Boost Time
22-47 Sleep Speed [Hz]
22-6* Broken Belt Detection
22-60 Broken Belt Function
22-61 Broken Belt Torque
22-62 Broken Belt Delay
30-** Special Features
30-2* Adv. Start Adjust
30-20 High Starting Torque Time [s]
30-21 High Starting Torque Current [%]
30-22 Locked Rotor Protection
30-23 Locked Rotor Detection Time [s]
32-** Motion Control Basic Settings
32-11 User Unit Denominator
32-12 User Unit Numerator
32-67 Max. Tolerated Position Error
32-80 Maximum Allowed Velocity
32-81 Motion Ctrl Quick Stop Ramp
33-** Motion Control Adv. Settings
33-00 Homing Mode
33-01 Home Oset
33-02 Home Ramp Time
33-03 Homing Velocity
33-04 Home Behaviour
33-41 Negative Software Limit
33-42 Positive Software Limit
33-43 Negative Software Limit Active
33-44 Positive Software Limit Active
33-47 Target Position Window
34-** Motion Control Data Readouts
34-0* PCD Write Par.
34-01 PCD 1 Write For Application
34-02 PCD 2 Write For Application
34-03 PCD 3 Write For Application
34-04 PCD 4 Write For Application
34-05 PCD 5 Write For Application
34-06 PCD 6 Write For Application
34-07 PCD 7 Write For Application
34-08 PCD 8 Write For Application
34-09 PCD 9 Write For Application
34-10 PCD 10 Write For Application
34-2* PCD Read Par.
34-21 PCD 1 Read For Application
34-22 PCD 2 Read For Application
34-23 PCD 3 Read For Application
33-24 PCD 4 Read For Application
33-25 PCD 5 Read For Application
33-26 PCD 6 Read For Application
33-27 PCD 7 Read For Application
33-28 PCD 8 Read For Application
33-29 PCD 9 Read For Application
33-30 PCD 10 Read For Application
34-5* Process Data
34-50 Actual Position
34-56 Track Error
37-** Application Settings
37-0* ApplicationMode
37-00 Application Mode
*[0] >Drive mode<
[1] >Position Control<
37-1* Position Control
37-01 Pos. Feedback Source
*[0] >24V Encoder<
37-02 Pos. Target
37-03 Pos. Type
37-04 Pos. Velocity
Appendix
VLT
®
Midi Drive FC 280
60 Danfoss A/S © 11/2015 All rights reserved. MG07A122