8Specifications
8.1 General Specifications
Normal overload 110% for 1 minute
Line power supply 200–240 V AC
Adjustable frequency drive
Typical Shaft Output [kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3
P3K7
3.7
IP 20 / Chassis A2 A2 A2 A3 A3
IP 21 / NEMA 1 A2 A2 A2 A3 A3
IP 55 / NEMA 12 A5 A5 A5 A5 A5
IP 66 / NEMA 12 A5 A5 A5 A5 A5
Typical Shaft Output [HP] at 208 V 1.5 2.0 2.9 4.0 4.9
Output current
Continuous
(3 x 200–240 V) [A]
6.6 7.5 10.6 12.5 16.7
Intermittent
(3 x 200–240 V) [A]
7.3 8.3 11.7 13.8 18.4
Continuous
kVA (208 V AC) [kVA]
2.38 2.70 3.82 4.50 6.00
Max. cable size:
(line power, motor, brake)
[mm
2
/AWG]
2)
4/10
Max. input current
Continuous
(3 x 200–240 V) [A]
5.9 6.8 9.5 11.3 15.0
Intermittent
(3 x 200–240 V) [A]
6.5 7.5 10.5 12.4 16.5
Max. pre-fuses
1)
[A]
20 20 20 32 32
Environment
Estimated power loss
at rated max. load [W]
4)
63 82 116 155 185
Weight enclosure IP20 [kg] 4.9 4.9 4.9 6.6 6.6
Weight enclosure IP21 [kg] 5.5 5.5 5.5 7.5 7.5
Weight enclosure IP55 [kg] 13.5 13.5 13.5 13.5 13.5
Weight enclosure IP66 [kg] 13.5 13.5 13.5 13.5 13.5
Efficiency
3)
0.96 0.96 0.96 0.96 0.96
VLT
®
HVAC Drive Instruction Manual 8 Specifications
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
8-1
8

Other manuals for Danfoss VLT