Line Power Supply 3 x 525–690 V AC
P132 P160 P200 P250
Typical Shaft output at 550
V [kW]
110 132 160 200
Typical Shaft output at 575
V [HP]
150 200 250 300
Typical Shaft output at 690
V [kW]
132 160 200 250
Enclosure IP21 D1 D1 D2 D2
Enclosure IP54 D1 D1 D2 D2
Enclosure IP00 D3 D3 D4 D4
Output current
Continuous
(at 550 V) [A]
162 201 253 303
Intermittent (60 sec over-
load)
(at 550 V) [A]
178 221 278 333
Continuous
(at 575/690 V) [A]
155 192 242 290
Intermittent (60 sec over-
load)
(at 575/690 V) [A]
171 211 266 319
Continuous KVA
(at 550 V) [KVA]
154 191 241 289
Continuous KVA
(at 575 V) [KVA]
154 191 241 289
Continuous KVA
(at 690 V) [KVA]
185 229 289 347
Max. input current
Continuous
(at 550 V) [A]
158 198 245 299
Continuous
(at 575 V) [A]
151 189 234 286
Continuous
(at 690 V) [A]
155 197 240 296
Max. cable size, line power
motor, load share and
brake [mm
2
(AWG)]
2 x 70 (2 x 2/0) 2 x 70 (2 x 2/0)
2 x 185 (2 x 350
mcm)
2 x 185 (2 x 350
mcm)
Max. external pre-fuses [A]
1
315 350 350 400
Estimated power loss
at rated max. load [W]
4)
,
575 V
2963 3430 4051 4867
Estimated power loss
at rated max. load [W]
4)
,
690 V
3430 3612 4292 5156
Weight,
Enclosure IP21, IP 54 [kg]
96 104 125 136
Weight,
Enclosure IP00 [kg]
82 91 112 123
Efficiency
4)
0.98
Output frequency 0–600 Hz
Heatsink overtemp. trip 185°F [85°C] 194°F [90°C] 230°F [110°C] 230°F [110°C]
Power card ambient trip 140°F [60°C]
8 Specifications VLT
®
HVAC Drive Instruction Manual
8-10
MG.11.A9.22 - VLT
®
is a registered Danfoss trademark
8

Other manuals for Danfoss VLT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT and is the answer not in the manual?

Danfoss VLT Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20, IP21, IP55, IP66
SeriesVLT
Control TechniqueFlux Vector Control
Output Voltage0-Vinput
Control MethodFieldbus
Communication InterfacePROFIBUS, CANopen
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Cooling MethodLiquid Cooled
Storage Temperature-25°C to +70°C
Relative Humidity5-95% non-condensing
AltitudeUp to 1000m (3280ft) without derating, up to 4000m (13120ft) with derating
Operating Temperature-10°C to +50°C (14°F to 122°F)