NOTE!
When carrying out manual initialization, serial communication, RFI filter settings and fault log settings are reset.
Removes parameters selected in par. 0-25
My Personal Menu
1. Disconnect from the line power and wait until the display
turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time as
powering up the Graphical LCP (GLCP).
2b. Press [Menu] while the LCP 101, Numerical Display is pow-
ering up.
3. Release the keys after 5 s.
4. The adjustable frequency drive is now programmed according
to default settings.
This parameter initializes all except:
par. 15-00
Operating Hours
par. 15-03
Power-ups
par. 15-04
Over Temps
par. 15-05
Over Volts
VLT
®
HVAC Drive Instruction Manual