MAGNET POWER SUPPLY SYSTEM 9100
30
DANFYSIK A/S - DENMARK.
AUX SETUP (Esc<AUX)
Special options can be initiated with the auxiliary switch set up 1.
Setting of bit 16 and 17 is intended for Offset DAC use. That is a 16 bit setting between 88 and
96% (Bit16=0 & BIT 17=1) or between 92% and 100% output current (Bit16=1 & BIT 17=1).
For linear DAC settings please set bit 16 & 17 to transparent mode.
Using the “WA” command a leading zeroes or trailing zeroes input format can be chosen.
- For leading zeroes: “WA 123" equals “WA 000123"
- For trailing zeroes: “WA 123" equals “WA 123000"
SW3 FOR AUXILIARY SETUP 1
ON
1
2 3
4
8
SW4
WA ZEROES
TRALING
A / V
%
LEADING
INTERLOCK CLEAR
CLEAR
OFF & CLEAR
DAC 17
TRANSPARENT
->0
->1
->1
DAC 16
->1
->0
->1
CAMAC TEST
NOT USED
UNI/BI-POLAR
DISPLAY UNITS
ON
1
2 3
4 5 6
7
8
#1
#1 AD Scaling factor must be set accordingly.
DISABLE {Hi Z}
ENABLE AS OUTPUT
UNIPOLAR
BIPOLAR
Parameters:
Default setting after “COLD BOOT”
DAC 16 & 17: Transparent
Interlock clear: OFF & CLEAR resets interlocks
“WA” Zeroes: WA command uses trailing zeroes.
( ): UNIPOLAR
Notice that UNI/BI-polar is a read-only parameter and cannot be changed by dip switch setting