4. CONTROLS
27
4.4.2 Time program Unit Configuration
When entering time program Unit Configuration, you will see the following start display in the
program D1-7:
Here you will find the following unit configuration points:
• FilterCheckDate (see 4.4.2.1)
• Heating_Coil (see 4.4.2.2)
• Closed_Mode_Cool (see 4.4.2.3)
• Signal_TP_External (see 4.4.2.4)
• Wake_Up_Temp (see 4.4.2.5)
• Wake_Up_Humid (see 4.4.2.5)
• BMS_SP_Control (see 4.4.2.6)
4.4.2.1 Filter Check Date
Under Filter Check Date the date for the annual filter check can be given in. The first or two
figures indicate the month, the next two figures indicate the day, when the filter check should
appear on the display. 912 for example stand for September the 12
th
.
4.4.2.2 Heating Coil
Under the point Heating Coil, you can configure if your unit is equipped either with water or
electrical heating coil.
4.4.2.3 Closed mode cooling
Under the point Closed Mode Cooling you can configure if your unit should cool (free and
active cooling) when the pool is closed or not. Normally this point is set to NO, but for
example in therapy pools, or hot countries it will be set to YES.
4.4.2.4 Signal TP External (PIR sensor or pool cover switch)
If you want to start or stop the unit with the help of an external contact, you can define this
under Signal_TP_External.
If a PIR sensor is used, you should set the point Signal_TP_External in one of the following
two modes: