EasyManua.ls Logo

Dantherm DanX 1 - 9.8 Technical Data DanX 2

Dantherm DanX 1
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9. APPENDIX
52
9.8 Technical data DanX 2
General
Air volume range high speed m
3
/h 1000 – 2000
Air volume nominal m
3
/h 1750
Supply air filter F7 / ePM1 55%
Exhaust air filter M5 / ePM10 70%
Heating coil RR 2 / 3
Coil connection “ 3/8
Drip tray connection “ 1
DanX 2 XD
Length mm 1570
Width mm 780
Height mm 1750
Weight kg 344
Electrical connection V 1 x 230 + N
Max full load current A 6.6
Max. power consumption kW 1.5
Max. main fuse A 10
DanX 2 HP
Length mm 1570
Width mm 780
Height mm 1750
Weight kg 379
Refrigerant kg 1.6 / R407c
GWP 1653
PED 1
WCC max flow l/h 800
Electrical connection V 2 x 400 + N
Max full load current A 7.0
Max. power consumption kW 1.6
Max. main fuse A 10