7. FAULTFINDING
43
7.1 Introduction
Normally an operation fault will give an alarm in the display of the control panel. For
details, please refer to section 4 Controls in this manual.
7.2 Fault finding
1)
If the frost thermostat is manual, you have to reset the thermostat before starting the
unit. The thermostat is normally located on the upper deck of the unit near the heating coil.
2)
The fire thermostat must be reset before the unit is started again. Press the red button
on the thermostat to reset. The thermostats are located in the exhaust (70°C thermostat)
and supply (40°C) air.
3)
The HP pressostat has to be reset before the
compressor can start again. The red reset
button (1) is placed inside the unit, just above
the compressor.
Alarm
Problem
Cause
Action
Service
Filter is dirty
Filter blocked
Change filter
Fan
Fan stopped
Thermal overload
Wait until motor has cooled
down. Start the unit. If fan
stops quickly again
change/repair motor
Frost
1)
Valve not opening
Defect actuator
Valve stuck
Change/Repair actuator
Change/Repair valve
No hot water
Pump not working
Boiler problem
Change/Repair pump
See boiler manual
Fire
2)
Return air
temperature > 40°C
Fire in the building
Check reason for high
temperature in return air
duct
Supply air
temperature > 70°C
After heating coil not
working correct at low
air volume
Fire in the unit
Check heating coil controls
HP/ LP
3)
Compressor
HP pressure over
24 bar
Air volume too small
Blockage in cooling
circuit
Outside temperature too
high
Check air volume
Check/repair cooling circuit
Reset pressure switch
LP pressure under
1.5 bar
Leakage in the cooling
circuit
Evaporator iced up
Repair cooling circuit
De-ice evaporator/check
de-icing function