7. FAULTFINDING
43
7.1 Introduction
Normally an operation fault will give an alarm in the display of the control panel. For
details, please refer to section 4 Controls in this manual.
7.2 Fault finding
1)
If the frost thermostat is manual, you have to reset the thermostat before starting the
unit. The thermostat is normally located on the upper deck of the unit near the heating coil.
2)
The fire thermostat must be reset before the unit is started again. Press the red button
on the thermostat to reset. The thermostats are located in the exhaust (70°C thermostat)
and supply (40°C) air.
3)
The HP pressostat has to be reset before the
compressor can start again. The red reset
button (1) is placed inside the unit, just above
the compressor.