31 • Mini dap4 User Manual
Set Point: The range is 70 to 90°F (factory setting is 80°F)
Note: If Hi Temp Alarm was set for NO – the Set Point will not appear on the screen
Press the ENTER key to advance to Lo Temp Alarm. The cursor will ash over the current setting. Press the UP or
DOWN key to change the setting.
Lo Temp Alarm: YES or NO (factory setting is YES)
Note: Choosing NO as the setting, the Low Temperature alarm will be disabled.
Press the ENTER key to advance to Set Point. The cursor will ash over the current setting. Press the UP or DOWN
key to change the setting.
Set Point: The range is 55 to 75°F (factory setting is 60°F)
Note: If Lo Temp Alarm was set for NO – the Set Point will not appear on the screen
Once a selection or selections have been made, move the cursor to the title block (Return Air Alarms) by pressing the
ENTER key
▼ Press the DOWN key to view the next screen:
The following will be displayed (values are for reference only):
Press the ENTER key to advance Hi Humidity Alarm. The cursor will ash over the current setting. Press the UP or
DOWN key to change the setting.
Hi Humidity Alarm: YES or NO (factory setting is YES)
Note: Choosing NO as the setting, the Hi Humidity alarm will be disabled.
Press the ENTER key to advance to Set Point. The cursor will ash over the current setting. Press the UP or DOWN
key to change the setting.
Set Point: The range is 35 to 90% RH (factory setting is 60% RH)
Note: If Hi Humidity Alarm was set for NO – the Set Point will not appear on the screen
Press the ENTER key to advance to Lo Humidity Alarm. The cursor will ash over the current setting. Press the UP
or DOWN key to change the setting.
Lo Humidity Alarm: YES or NO (factory setting is YES)
Note: Choosing NO as the setting, the Lo Humidity alarm will be disabled.
Press the ENTER key to advance to Set Point. The cursor will ash over the current setting. Press the UP or DOWN
key to change the setting.
Humidity Alarm
Hi Humidity Alarm: Yes
Set Point: 60%
Lo Humidity Alarm: Yes
Set Point: 40%