DKG-329 User Manual V-12 (09.10.2012)
- 4 -
WARNING: ELECTRICITY CAN KILL
ALWAYS disconnect the power BEFORE
connecting the unit.The fuse rating should be 6
Amps.
1) ALWAYS remove the plug connectors when inserting wires with
a screwdriver.
2) An appropriate and readily accessible set of disconnection
devices (e.g. automatic fuses) MUST be provided as part of the
installation.
3) The building mains supply MUST incorporate appropriate short-
circuit backup protection (e.g. a fuse or circuit breaker) of High
Breaking Capacity (HBC, at least 1500A).
Use cables of adequate current carrying capacity (at least
0.75mm
2
) and temperature range.
WARNING: THE UNIT IS NOT FUSED.
Use external fuses for Mains phases: L1,L2,L3,
Generator phase: L1,L2,L3, Battery positive: BAT(+).
Install the fuses as nearly as possible to the unit in a
place easily accessible for the user.