6  STANDARD PROGRAMMING
WARNING  For reversible motors with electromagnetic brake, remember to set P062=3.
1  Power Supply
When turned on, “ ”, “ ” (or the current rmware version) “ ”, “ ” (or the selected Type) appear on the display in 
sequence followed by the closed gate symbol “- - - - ”.
* If the control panel has already been programmed and the power fails or is switched off  - once power is returned and a START command 
is given, the position reset procedure is performed (see “rESP” in the table “WORKING STATUS MESSAGES” on page 51.
2  Visualisation of inputs and operations-counter status
1.  Scroll the parameters with the   and   keys until the 
screen reads P013;
2.  Access the parameter by pressing the   button;
3.  The “Input Status” is shown on the screen (check that this 
is correct):
 
4.  Press the   button again;
5.  The “Total Operation Counter” 
 appears on the 
screen followed by the   multiplier.
To calculate the number of completed operations, the two 
values must be multiplied.
I.e.: 
 = 120x10 = 1200  operations completed
6.  Press the 
 button again;
7.  The “Total Maintenance Counter” 
 appears on the 
screen followed by the   multiplier.
To calculate the number of operations remaining before 
the maintenance request, the two values must be 
multiplied.
I.e.: 
 = 1500x1 = 1500  operations yet to be 
completed before the maintenance request
8.  Press the 
 button again to exit the parameters (P013 is 
shown on the screen again).