Analogue controller or EIC, J1939
As an initial setting before the first start up, the K
p
, Ti and Td of the frequency and power controllers are set
to a value giving a slow regulation. This means that K
p
and Td should be set to a low value, and Ti should be
set to a high value.
4.1.7 Voltage controller settings
The voltage controller settings are adjusted in the regulation part of the control setup menu.
The screendump above illustrates the controller settings of the voltage and reactive power controller. As an
initial setting before the first start up, the K
p
of the voltage and reactive power controllers are set to a low
value giving a slow regulation.
Analogue controller or J1939
As an initial setting before the first start up, the K
p
, Ti and Td of the frequency and power controllers are set to
a value giving a slow regulation. This means that K
p
and Td should be set to a low value, and Ti should be
set to a high value.
General guidelines for commissioning
4189340703 UK
Settings
DEIF A/S Page 12 of 25

Table of Contents

Other manuals for Deif GPU-3 Hydro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deif GPU-3 Hydro and is the answer not in the manual?

Deif GPU-3 Hydro Specifications

General IconGeneral
BrandDeif
ModelGPU-3 Hydro
CategoryController
LanguageEnglish

Related product manuals