2.2.2 Parameter settings - system setup
The PC utility software is a software program that can be used for configuration of the Multi-line 2 products.
There are two versions, 1.x for PPU-2 and 3.x. for PPU-3.
The utility software can be downloaded at www.deif.com.
The table below shows a direct conversion of the parameters that include nominal settings.
Nominal settings
Parameter
PPU-2
Descrip-
tion
Address Value Parameter
PPU-3
Descrip-
tion
Address Value
4011 Nom. fre-
quency
182 Hz 6001 Nom. f (1) 407 Hz
4012 Nom. pow-
er
183 kW 6002 Nom. P (1) 408 kW
4013 Nom. cur-
rent
184 A 6003 Nom. I (1) 409 A
4014 Nom. volt-
age
185 V 6004 Nom. U (1) 410 V
N/A 6005 Nom. RPM
(1)
411 RPM
4021 Volt. prim.
GEN
186 V 6041 G primary
U
428 V
4022 Volt. sec.
GEN
187 V 6042 G secon-
dary U
429 V
4023 Current
prim.
188 A 6043 G primary I 430 A
4024 Current
sec.
189 A 6044 G secon-
dary I
431 A
4031 Volt. prim.
BUS
190 V 6051 BB primary
U1
432 V
4032 Volt. sec.
BUS
191 V 6052 BB secon-
dary U1
433 V
4033 Nom. volt.
BUS
421 V 6053 BB nominal
U1
1326 V
ML-2 application notes Converting PPU-2
to PPU-3 4189341126 UK