2.2.6 Synchronisation setup
The table below shows which parameters that are to be configured when setting the synchronisation.
Synchronisation setup
Parameter
PPU-2
Description Address Parameter
PPU-3
Description Address
2021 Sync. dfMax 71 2021 Sync. dfMax 65
2022 Sync. dfMin 72 2022 Sync. dfMin 66
2023 Sync. duMax 73 2023 Sync. duMax 67
2024 Sync. t CB 74 2024 Sync. t GB 68
2041 Blackout dfMax 80 2111 Blackout dfMax 94
2042 Blackout duMax 81 2112 Blackout duMax 95
2043 Blackout ena-
ble
82 2113 Sync. blackout
enable
96
2.2.7 Protection setup
The following adjustment points are available in PPU-2: Set points, delay timer, output A or B. The protection
has a commissioning window where live status is shown.
ML-2 application notes Converting PPU-2
to PPU-3 4189341126 UK
Application and installation