Slot #4, not used
Slot #5, AC measuring
Term. Function Technical data Description
73 I L1 s1 Busbar current L1 1/5 A AC input
74 I L1 s2
75 I L2 s1 Busbar current L2 1/5 A AC input
76 I L2 s2
77 I L3 s1 Busbar current L3 1/5 A AC input
78 I L3 s2
79 U L1 Bus 1 voltage L1 Max. 690V AC phase - phase value
80 Not used
81 U L2 Bus 1 voltage L2 Max. 690V AC phase - phase value
82 Not used
83 U L3 Bus 1 voltage L3 Max. 690V AC phase - phase value
84 U neutral Not used
85 U L1 Bus voltage L1 Max. 690V AC phase - phase value
86 Not used
87 U L2 Bus voltage L2 Max. 690V AC phase - phase value
88 U neutral Not used
89 U L3 Bus voltage L3 Max. 690V AC phase - phase value
Current inputs are galvanically separated. Max. 0.3 VA per phase. Voltage