EasyManua.ls Logo

Deif PPU - Page 49

Deif PPU
69 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PPM Installation Instructions
DEIF A/S Page 49 of 69
Slot #4, not used
Slot #5, AC measuring
Term. Function Technical data Description
73 I L1 s1 Busbar current L1 1/5 A AC input
74 I L1 s2
75 I L2 s1 Busbar current L2 1/5 A AC input
76 I L2 s2
77 I L3 s1 Busbar current L3 1/5 A AC input
78 I L3 s2
79 U L1 Bus 1 voltage L1 Max. 690V AC phase - phase value
80 Not used
81 U L2 Bus 1 voltage L2 Max. 690V AC phase - phase value
82 Not used
83 U L3 Bus 1 voltage L3 Max. 690V AC phase - phase value
84 U neutral Not used
85 U L1 Bus voltage L1 Max. 690V AC phase - phase value
86 Not used
87 U L2 Bus voltage L2 Max. 690V AC phase - phase value
88 U neutral Not used
89 U L3 Bus voltage L3 Max. 690V AC phase - phase value
Current inputs are galvanically separated. Max. 0.3 VA per phase. Voltage
measurements are available (phase to phase) from 100V AC to 690V AC.