Environmental
For additional information about environmental measurements for specic storage system congurations, see dell.com/
environmental_datasheets.
Temperature
Operating 10°C (50°F) to 35°C (95°F) with a maximum temperature gradation of 20°C/
hour (36°F/hour)
Operating above 35°C could result in data loss
Storage –40° to 65°C (–40° to 149°F) at a maximum altitude of 12,000 m (39,370 ft)
Relative humidity
Operating 10% to 80% (noncondensing) with 29°C (84.2°F) maximum dew point
Storage 5% to 95% (noncondensing) with 33°C (91°F) maximum dew point
Maximum vibration
Operating 0.21 G at 5–500 Hz for 15 min
Storage 1.04 G at 2–200 Hz for 15 min
Maximum shock
Operating 31 G +/- 5% with pulse duration of 2.6 ms +/- 10% (equivalent to 20 in./sec [51
cm/sec])
Storage 71 G +/- 5% with pulse duration of 2 ms +/- 10% (equivalent to 35 in./sec [89
cm/sec])
Altitude
Operating 3,048 m (10,000 ft)
≤35°C (95°F) Maximum Rating – Maximum temperature is reduced by
1°C/300 m (1°F/547 ft) above 950 m (3,117 ft)
Storage 12,000 m (39,370 ft)
Airborne Contaminant Level
Class G1 or lower as dened by ISA-S71.04-1985
22
SCv3000 and SCv3020 Storage System Technical Specications