11 - 10 Treatment of Fixed Amount Circulation Malfunction
Factory Setting: 00
Settings
00: Turn off all motors
01: Turn off AC drive
This parameter determines treatment of AC drive malfunction during fixed amount
circulation.
When AC drive occurs power circuit malfunction to make auxiliary power disable and
microprocessor can’t work, all output will close automatically.
11 - 11 Stop Frequency of Auxiliary Motor
Factory Setting: 0.00
Settings 0.00~120.00Hz Unit: 0.01Hz
If output frequency of AC drive is less than or equal to this parameter when AC drive is fixed
amount circulation
(11-01=02) or fixed amount (11-01=03), AC drive will make motor stop in
sequence.