08 - 18  Automatic Voltage Regulation (AVR) 
Factory Setting: 00
 Settings 
00: AVR function enabled 
01: AVR function disabled 
02: AVR function disabled for deceleration 
  This parameter determines the function of Automatic Voltage Regulation is enabled or 
disabled. 
  This parameter is set to 01: when AVR function is disabled, AC drive will calculate input 
voltage by DC Bus value (620VDC). Output voltage will vary by DC Bus varying and may 
cause output current insufficiently, over current or oscillation.  
  This parameter is set to 00: when AVR function is enabled, AC drive will calculate output 
voltage by actual voltage value of DC Bus. Output voltage won’t vary by DC Bus varying.  
  This parameter is set to 02: AC drive will disable AVR function during decelerate to stop. It 
can speed up braking in some degree. 
08 - 19 
Software Setting of the Brake Level  
(the action level of the brake resistor) 
a 
Factory Setting:  380.0/ 
760.0
  Settings 
230V series: 370.0 ~ 410.0VDC 
460V series: 740.0 ~ 820.0VDC 
00: Disable 
Unit:  0.1
  This parameter determines software setting of the brake level. 
  The model VFD007~150F43A has brake chip, user could select suitable brake resistor to 
have the best deceleration characteristics.  
  The action level of the brake resistor could be set by this parameter.  
08 - 20  Vibration Compensation Factor 
a 
Factory Setting:  00
   Settings  00~1000  Unit:  1
  This parameter will minimize vibration at low speed during vector control.  The value of the 
parameter is a GAIN.  The higher the value, the more vibration dampening that will occur.