02 - 06 Line Start Lockout
Factory Setting: 01
Settings 00: Disabled
01: Enabled
When enabled, the AC drive will not start when powered up with a run command applied.
The AC drive must see the run command transition from stop to run after power up. When
Line Start Lockout is disabled (also known as Auto-Start), the AC drive will start when
powered-up with run commands applied.
02 - 07 Loss of ACI Signal
Factory Setting: 01
Settings 00: Decelerate to 0Hz
01: E.F.
02: Continue operation by the last frequency command
This parameter determines the AC drives response to a loss of the ACI input.
02 - 08 Start-up Display Selection
a
Factory Setting: 00
Settings Bit0~1: 00 = F LED
01 = H LED
10 = U LED (special display)
11 = Fwd / Rev
Bit2: 0 = Fwd LED / 1 = Rev LED
Bit3~5: 000 = 1st 7-step
001 = 2nd 7-step
010 = 3rd 7-step
011 = 4th 7-step
100 = 5th 7-step
Bit6~7: Reserved
This parameter determines the display on keypad after each power up.
To program this parameter the user must first generate a Hex value with the information
above. Then using the Hex to Decimal conversion to find the corresponding Decimal value
and enter it into this parameter.
For example, a setting of 21 (decimal 21= hex 010101) will display the “H” and “REV” LEDs
and the cursor will stay at the 3rd 7-step display upon power up.
When setting to U LED, please refer to 02-09.