VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-42
Master frequency command
Output frequency
Output voltage
output current
Synchronization attained
Time
08-07
Output voltage
Output frequency
Actual V/F output
V/F curve setting
08 - 08 BB Speed Search Method
Factory Setting: 00
Settings
00: Trace from top downward
01: Trace from bottom upward
This parameter determines BB speed search method when multi-function input terminal
04-00 to 04-07 is set to BB External interrupt (11 or 12) and activates.
BB speed search method is the same with restart speed search after momentary loss
power.
08 - 09 Auto Restart Times After Fault
Factory Setting: 00
Settings 00 ~10
This parameter determines the times of auto restart after fault.
When AC drive occurs fault (OV, OC or OCC) and fault disappeared automatically, this
parameter allows AC drive reset and runs with the parameter that is set before fault
occurred.
If fault occurred times exceed 08-09 setting, AC drive will reject to restart and need to reset
by users to keep on running.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics AC Drive VFD-F Series and is the answer not in the manual?

Delta Electronics AC Drive VFD-F Series Specifications

General IconGeneral
BrandDelta Electronics
ModelAC Drive VFD-F Series
CategoryInverter
LanguageEnglish