EasyManuals Logo

Delta AS16AP11P-A User Manual

Delta AS16AP11P-A
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #297 background imageLoading...
Page #297 background image
Chapter 9 Ethernet Specification and Operation
9-89
9_
Instance
Attribute
Name
Access
Rule
Data
Type
Values Description
H’00 D0.0 Set
BOOL
H’00 D0.0 bit register
H’01 D0.1 Set
BOOL
H’00 D0.1 bit register
H’02-H’752FE D0.2-D29999.14 Set
BOOL
H’00 D0.2-D29999.14 bit register
H’752FF D29999.15 Set
BOOL
H’00 D29999.15 bit register
When Instance = 2, the Instance Attributes are listed below.
Instance
Attribute
Name
Access
Rule
Data
Type
Values Description
H’00 D0 Set INT H’00 D0 word register
H’01 D1 Set INT H’00 D1 word register
H’02-H’752E D2-D29998 Set INT H’00 D2-D29998 word register
H’752F D29999 Set INT H’00 D29999 word register
9.8.13 M Register (Class ID: 353 Hex)
Service Code
Service Code Service Name
Support
Description
Class Attribute
Instance
Attribute
H’0E Get_Attribute_Single X V Read one attribute
H’10 Set_Attribute_Single X V Write one attribute
H’32 Read_Parameter X V Read Parameter
H’33 Write_Parameter X V Write Parameter
Class
Class IDH’353
Instance
H’01Instance Attribute, Bit Register
When Instance = 1, the Instance Attributes are listed below.