AS Series Operation Manual
12-8
_12
Error
Code
(16#)
Description Solution Flag Log
is 32).
140E
More than eight remote modules on
the right side of the CPU module.
Check the total number of remote modules on the right
side of the CPU module (maximum is 8).
SM30
V
1600
The extension module ID exceeds
the range.
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the error still occurs, contact the factory.
SM10
V
1601
The extension module ID cannot be
set.
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the error still occurs, contact the factory.
SM10
V
1602
The extension module ID is
duplicated.
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the error still occurs, contact the factory.
SM10
V
1603
The extension module cannot be
operated.
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the error still occurs, contact the factory.
SM10
V
1604
Extension module communication
timeout
1. Make sure the module is properly connected to the
CPU module and turn the modules on again.
2. If the error still occurs, contact the factory.
SM10
V
1605 Hardware failure Contact the factory. SM10
V
1606
Errors on the communication
module function card
Make sure the function card is properly connected to the
CPU module and turn the modules on again.
SM10
V
1607 The external voltage is abnormal.
Check whether the external 24 V power supply to the
module is normal.
SM10
V
1608
The Internal factory calibration or
the CJC is abnormal.
Contact the factory. SM10
V
1609
-
160F
Reserved (Error codes for the extension modules)
200A Invalid instruction
Check the syntax error step in the program. Modify and
compile the program and then download the program
again.
SM5 V
6010
The number of MODBUS TCP
connections exceeds the range.
Check the number of superior devices (maximum is 32).
SM
1092
V
6011
The number of EtherNet/IP
connections exceeds the range.
Check the number of connections (maximum is 16).
SM
1093
V
C000
-
CFFF
The program syntax is incorrect.
Save the PLC program and hand the file to the company
or the technicians.