ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-159
Range
-5000 ~ 5000
Data Size
16-bit
Format
Decimal
Settings
Users manually adjust the OFFSET
P4-23 TAO Analog Torque Input OFFSET
Address: 042EH
042FH
Operational
Interface
Panel / Software Communication
Related Section: -
Default
0
Control
Mode
T
Unit
mV
Range
-5000 ~ 5000
Data Size
16-bit
Format
Decimal
Settings
Users manually adjust the OFFSET
220V Series
P4-24 LVL Level of Under voltage Error
Address: 0430H
0431H
Operational
Interface
Panel / Software Communication
Related Section: -
Default
160
Control
Mode
ALL
Unit
V (rms)
Range
140~190
Data Size
16-bit
Format
Decimal
Settings
When the voltage of DC BUS is lower than P4-24*
2
, the under
voltage alarm occurs.