EasyManua.ls Logo

Delta ASD-A2-2043 Series - Page 298

Delta ASD-A2-2043 Series
721 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-47
Settings
Polarity of monitor analog output
Polarity of encoder pulse output
Not in use
Polarity of monitor analog output
0: MON1(+), MON2(+) 2: MON1(-), MON2(+)
1: MON1(+), MON2(-) 3: MON1(-), MON2(-)
Polarity of encoder pulse output
0: Forward output 1: Reverse output
P1-04 MON1 MON1 Analog Monitor Output Proportion
Address: 0108H
0109H
Operational
Interface
Panel / Software Communication
Related Section:
6.4.4
Default
100
Control
Mode
ALL
Unit
% (full scale)
Range
0 ~ 100
Data Size
16-bit
Format
Decimal
Settings
Please refer to parameter P0-03 for the setting of analog output
selection.
For example:
P0-03 = 0x00 (MON1 is the speed analog output)
When the output voltage value of MON1 is V1:
Motor speed = (Max. speed × V1/8) × P1-04/100
P1-05 MON2 MON2 Analog Monitor Output Proportion
Address: 0108H
0109H
Operational
Interface
Panel / Software Communication
Related Section:
6.4.4
Default
100
Control
Mode
ALL

Table of Contents