ASDA-M Chapter 8 Parameters
Revision December, 2014 8-105
Description of Auto Mode Setting:
When it is set to 1: Auto resonance, the value returns to 0
automatically and saves the point of
resonance suppression when it is stable. If
it is unstable, re-power on or set back to 1
for re-estimation again.
When it is set to 2: Continuous suppression automatically. When
it is stable, the point of resonance
suppression will be saved. If it is unstable,
re-power on for re-estimation.
When switching to mode 0 from mode 2 or 1, the setting of P2-43,
P2-44, P2-45 and P2-46 will be saved automatically.
P2-48 ANCL
Resonance Suppression Detection
Level
Address: 0260H
0261H
Parameter
Attribute:
Parameter for individual axis
Related Section: -
Operational
Interface:
Panel / Software Communication
Default:
100
Control
Mode:
ALL
Unit:
-
Range:
1 ~ 300%
Data Size:
16bit
Format:
DEC
Settings:
(The smaller the setting value is, the more sensitive the
resonance wil be.)
P2-48 ↑, resonance sensitiveness ↓
P2-48↓, resonance sensitiveness ↑