DVP-ES3 Series Operation Manual
12-8
2014
The task designated by the TKON or
YKOFF instruction is incorrect or
exceeds the range.
Check the program, compile the program again,
and download the program again.
SM0 V
2017
The instruction BREAK is written outside
of the FOR-NEXT loop.
Check the program, compile the program again,
and download the program again.
SM0 V
2027
No such position planning table number
or the format is incorrect.
1. Check the program, compile the program again,
and download the program again.
2. Check the settings of the position planning table.
SM0 V
2028
High speed output instruction is being
executed. Only one instruction can be
executed at a time.
Refer to SR28 for the record of the
rearrange the output control procedures.
-
V
6004 The IP address filter is set incorrectly.
Set the Ethernet parameter for the CPU module in
SM1108 X
RJ45 port is not connected.
6012
There are devices using the same IP
address.
1. Check if there are devices using the same IP
address.
2. Check if there is more than 1 DHCP or BOOTP
SM1101 V
6100 The email connection is busy.
Retry the email connection later. Thi
cause the PLC to stop running. Solve the problem
by means of the related flag in the program.
SM1113 X
6103
The trigger attachment mode in the
email is set incorrectly.
Set up the trigger attachment mode in HWCONFIG
> CPU Module > Device Setting > Options >
Ethernet Port Advanced > Email > Trigger Setting >
Trigger Attachment Mode.
SM1113 X
6104
The attachment in the email does not
Check whether the attachment exists in the
SM1113 X
6105
The attachment in the email is
oversized.
Check the size of the attachment. If the size is over
2 MB, the file cannot be sent as an attachment.
SM1113 X
6106
There is an SMTP server response
timeout.
Check for the correct address and set up the SMTP
server in HWCONFIG > CPU Module > Device
Setting > Options > Ethernet Port Advanced >
SM1113 X
6107
There is an SMTP server response
timeout.
1. Check whether the status of the SMTP server is
normal.
2. Retry sending of the email later. This error does
not cause the PLC to stop running. Solve the
problem by means of the related flag in the
program.
SM1113 X
6108 SMTP verification failed
Check for the correct ID/Password and set up in
HWCONFIG > CPU Module > Device Setting >
Options > Ethernet Port Advanced > Email again.
SM1113 X
6200
The remote communication IP address
set in the TCP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > TCP
Socket.
- X
6201
The local communication port set in the
TCP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
- X