DVP-ES3 Series Operation Manual
12-10
_12
6210
The data received through the UDP
socket exceeds the device range.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
- X
6212
There is no response from the remote
device after the timeout period.
Make sure that the remote device is connected. - X
6213 The data received exceeds the limit.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
- X
6214
The remote device refuses the
connection.
Make sure the remote device operates normally. - X
6215 The socket is not opened.
Check whether operational sequence in the
program is correct.
- X
6217 The socket is opened.
Check whether operational sequence in the
program is correct.
- X
6218
The data has been sent through the
socket.
Check whether operational sequence in the
program is correct.
- X
6219
The data has been received through the
socket.
Check whether operational sequence in the
program is correct.
- X
621A The socket is closed.
Check whether operational sequence in the
program is correct.
- X
7011
The device communication function
code in COM1 is incorrect.
1. Check the communication setting in the master
and the slave.
2. Check the communication cable.
- H
7012
The device communication address
used in COM1 is incorrect.
1. Check the communication setting in the master
and the slave.
2. Check the communication cable.
- H
7013
The device used in COM1 exceeds the
device range.
1. Check the communication setting in the master
and the slave.
2. Check the communication cable.
- H
7014
The device length of the
communication
data in COM1 exceeds the limit.
1. Check the communication setting in the master
and the slave.
2. Check the communication cable.
- H
7017
The device checksum for the
communication serial port of COM1 is
incorrect.
1. Check the communication setting in the master
and the slave.
2. Check the communication cable.
- H
7021
The device communication function
code in COM2 is incorrect.
1. Check the communication setting in the master
and the slave.
2. Check the communication cable.
- H
7022
The device communication address
used in COM2 is incorrect.
1. Check the communication setting in the master
and the slave.
2. Check the communication cable.
- H
7023
The device used in COM2 exceeds the
device range.
1. Check the communication setting in the master
and the slave.
2. Check the communication cable.
- H

Table of Contents

Other manuals for Delta DVP-ES3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DVP-ES3 Series and is the answer not in the manual?

Delta DVP-ES3 Series Specifications

General IconGeneral
BrandDelta
ModelDVP-ES3 Series
CategoryController
LanguageEnglish

Related product manuals