ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-79
P1-55 MSPD Maximum Speed Limit
Address: 016EH
016FH
Operational
Interface
Panel / Software Communication
Related Section: -
Default
Same as the rated speed of each model
Control
Mode
ALL
Unit
r/min
Range
0 ~ max.speed
Data Size
16-bit
Format
Decimal
Settings
The default of the max. speed of servo motor is set to the rated speed.
P1-56 OVW Output Overload Warning Level
Address: 0170H
0171H
Operational
Interface
Panel / Software Communication
Related Section: -
Default
120
Control
Mode
ALL
Unit
%
Range
0 ~ 120
Data Size
16-bit
Format
Decimal
Settings
The setting value is 0 ~ 100, if the servo motor continuously outputs
the load and is higher than the setting proportion (P1-56), the early
warning for overload (DO is set to 10, OLW) will occur.
If the setting value is over 100, it will disable this function.
P1-57 CRSHA Motor Crash Protection (torque percentage)
Address: 0172H
0173H
Operational
Interface
Panel / Software Communication
Related Section: -
Default
0
Control
Mode
ALL