Figure 5-2 : AC plug illustration (96.031.4154.3 01K, Wieland Electric GmbH)
Screw connection :
Tightening torque
typ. 4+1 N.m
1.
2.
1.
2.
Detail
5.2.1.2 AC plug of H5A_222
The AC plug provided with the inverter has the following technical characteristics:
Technical data
noitcetorp fo eergeD
Nominal current
(observe derating*)
ssorc rotcudnoc -
section:
6 mm²
²mm 4
²mm 5.2
2.5 mm² with 1.5 mm² field plug
egatlov lanimoN
egatlov egrus detaR
eerged noitulloP
erutarepmet gnitarepO
lairetaM
66PI
**
/ IP68 (2 m, 24 h)
**
/ IP69K
***
IEC 61984 IEC 61535 2 PfG 1915
@ 85 °C
35 A 32 A 21,4 A
A 3.71A 52A 23
A 1,41A 02A 42
17,5 A 17,5 A 12,2 A
8322 LU5191 GfP 253516 CEI48916 CEI
690 V 500 V 500 V 600 V
Vk 6
3
-40 °C ... +110 °C -40 °C ... +110 °C-40 °C ... +110 °C-40 °C ... +105 °C
EPP
** TÜV Rheinland approved / *** Phoenix Contact approved
* Operating current [A] depending on ambient temperature [°C], according to conductor cross-section.
Power rating Upstream AC circuit breaker
H5A
_222 5 kVA 25A
Table 5-2: Recommended upstream protection
19