EasyManuals Logo

Delta H2.5 User Manual

Delta H2.5
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
Inverter
response
Allowed range
Australia A
Australia B
Australia C
Increase in
frequency
response
Upper limit
-
52
52
55
55New Zealand
Decrease in
frequency
response
Lower limit Hz
-
47
47
45
45
Lower limit of
continuous
operation
range (fLLCO) Hz
49.5 - 49.9
49.75
49.85
49.5
49.8
Upper limit of
continuous
operation
range (fULCO) Hz
50.1- 50.5
50.25
50.15
50.5
50.2
Inverter
response
Allowed range
Australia A
Australia B
Australia C
New Zealand
Frequency where power output
level is maximum(f
Pmax) Hz
Decrease in frequency
response limit
47 - 49
48
48
47
48
Increase in frequency
response limit
Frequency where power output
level is minimum(f
Pmin) Hz
52
52
53
52
51 - 53
Frequency variation withstand limits
Frequency response limits
30
Active/Reactive Power Control and LVRT (Optional)

Other manuals for Delta H2.5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta H2.5 and is the answer not in the manual?

Delta H2.5 Specifications

General IconGeneral
BrandDelta
ModelH2.5
CategoryInverter
LanguageEnglish

Related product manuals