Figure 3-14: DC wiring illustration
H4CMC4D-MSH4CFC4D-MS
M30A_230 uses H4 type connectors mounted on the bulkhead to connect the
string to the inverter. Mating connectors (See Figure 3-14) are provided within
the packing.
The polarities of DC wiring are divided into positive and negative, layout of the
connectors is shown as Figure 3-15.
Ensure the DC conductors used are Cu and sized to the correct ampacity per
NEC or other local code
• Strip off all wires for 6.5~7.5 mm.
• The cross-sectional area for each DC conductor is 12~10 AWG (4~6 mm²).
Choose the DC string wire size based on NEC requirements or other local code.
Please read the following instructions for connecting DC connector :
29
Installation