M60U
Operation and Installation Manual
Grid-tie Transformerless Solar Inverter
The power behind competitiveness
www.deltaww.com

Table of Contents

Questions and Answers

  • C
    Christina ChapmanSep 5, 2025
    What does HW COMM1 (F23) error mean on my Delta M60U Inverter?
    • K
      Kimberly SheltonSep 5, 2025
      If your Delta Inverter displays 'HW COMM1 (F23)', it could be due to: 1. DSP is idling, so contact customer service for technical support. 2. The communication connection is disconnected, so check the connection interface RS-485. 3. The communication circuit is malfunction, so check the communication card.
  • M
    Mrs. Michelle FisherSep 4, 2025
    What does HW Eff. (F20) error mean on my Delta M60U Inverter?
    • D
      Destiny LeeSep 4, 2025
      If your Delta Inverter is showing 'HW Eff. (F20)', the possible causes are: 1. The calibration is incorrect, so check the accuracy of current and power. 2. The current feedback circuit is defective, so check the current feedback circuit inside the inverter.
  • J
    jennifer98Aug 25, 2025
    What to do if my Delta M60U Inverter shows AC Volt High (E11, E13, E16, E18, E21, E23)?
    • C
      Cynthia BrennanAug 25, 2025
      If the Delta Inverter shows 'AC Volt High' (E11, E13, E16, E18, E21, E23), it could be due to several reasons. First, the actual utility voltage might be over the OVR setting, so check the utility voltage. Second, the utility voltage might be over the Slow OVR setting during operation, so check the Grid code and Grid setting. Third, the Grid code or Grid setting might be incorrect, so check the connection in the AC terminal. If none of these solves the problem, there may be a detection circuit malfunction, and you should contact customer service for technical support.
  • J
    Janet OdonnellSep 3, 2025
    What does HW Red ADC1 (F18) error mean on my Delta Inverter?
    • J
      Jaclyn FranklinSep 4, 2025
      If your Delta Inverter is showing a 'HW Red ADC1 (F18)' error, it may be caused by: 1. Insufficient input power, so check the input voltage, which must be >150Vdc. 2. Auxiliary power circuitry malfunction, so check the auxiliary circuitry inside the inverter. 3. A detection circuit malfunction, and you should contact customer service for technical support.
  • J
    Jennifer RussellSep 3, 2025
    What does HW DSP ADC3 (F17) error mean on my Delta Inverter?
    • S
      sjohnsonSep 3, 2025
      If your Delta Inverter displays 'HW DSP ADC3 (F17)', the issue might be: 1. Insufficient input power, so check the input voltage, which must be >150Vdc. 2. Auxiliary power circuitry malfunction, so check the auxiliary circuitry inside the inverter. 3. A detection circuit malfunction, and you should contact customer service for technical support.
  • J
    Julie ThomasSep 3, 2025
    What does HW DSP ADC2 (F16) error indicate on my Delta M60U?
    • J
      Jennifer RobertsSep 3, 2025
      If your Delta Inverter displays 'HW DSP ADC2 (F16)', it could be due to: 1. Insufficient input power, so check the input voltage, which must be >150Vdc. 2. Auxiliary power circuitry malfunction, so check the auxiliary circuitry inside the inverter. 3. A detection circuit malfunction, and you should contact customer service for technical support.
  • T
    Tommy RiosSep 2, 2025
    What causes HW DSP ADC1 (F15) error on Delta Inverter?
    • E
      elizabethbruceSep 2, 2025
      If your Delta Inverter is showing 'HW DSP ADC1 (F15)', the possible causes are: 1. Insufficient input power, so check the input voltage, which must be >150Vdc. 2. Auxiliary power circuitry malfunction, so check the auxiliary circuitry inside the inverter. 3. A detection circuit malfunction, and you should contact customer service for technical support.
  • E
    Erica RiceSep 2, 2025
    What does HW RLY (F13) mean on a Delta M60U?
    • E
      Eric DeleonSep 2, 2025
      If your Delta Inverter displays 'HW RLY (F13)', potential causes include: 1. The driver circuit for the relay being defective, so check the input voltage, which must be >150Vdc. 2. The relay(s) being defective, so replace the defective relay. 3. A detection circuit malfunction (Inverter voltage), and you should contact customer service for technical support.
  • C
    campbellstephenSep 1, 2025
    What causes Grid Quality (E07) error on Delta Inverter?
    • M
      Melissa ScottSep 1, 2025
      If your Delta Inverter displays 'Grid Quality (E07)', it may be caused by non-linear load in Grid and near to inverter. In this case grid connection of inverter need to be far away from non-linear load if necessary.
  • E
    edwardberrySep 1, 2025
    What does HW NTC4 Fail (F10) error mean on my Delta Inverter?
    • K
      Kathleen LopezSep 1, 2025
      If your Delta Inverter is showing 'HW NTC4 Fail (F10)', it may be caused by: 1. Ambient temperature >90 ? or

Summary

Safety

Information of the Inverter

Provides legal provisions and identifies the target audience for the manual.

General Safety

Covers essential safety practices, warnings, and symbols for safe operation.

Introduction

Valid Model

Lists the supported inverter model numbers for which this manual is applicable.

Product Overview

Details the inverter's components, models, and general features with diagrams.

Installation

Mechanical Installation

Guides on physical mounting of the inverter, including wall and tilt options.

Electrical Installation for AC Wiring

Covers AC wiring procedures, connections, and required devices for grid connection.

Electrical Installation for DC Wiring

Covers DC wiring procedures, connections, and grounding for PV array inputs.

Communication Module Connections

Explains how to connect communication modules and RS-485 interfaces.

Commissioning

First startup

Outlines the initial setup routine for language, grid code, and ID settings.

Main Menu Functions

Introduces the inverter's operational menu, including monitoring and settings.

Install Settings

Accesses critical configuration parameters like Inverter ID, Grid Code, and Grid Settings.

Maintenance

Removing and re-installing the Wiring Box (WB) cover

Provides procedures for accessing the inverter's internal components.

Component Replacement

Procedures for replacing SPD, fuses, and fans, ensuring system integrity.

De-Commissioning

Outlines the safe procedure for removing the inverter from operation.

Error message and Trouble Shooting

Error, Warning, and Fault Codes

Lists common error messages, their causes, and troubleshooting actions.

Calling for Help

Provides information required for contacting technical support efficiently.

Technical Information

M80 U Series Specifications

Lists detailed technical specifications for the M80U inverter models.

M60 U Series Specifications

Lists detailed technical specifications for the M60U inverter models.

APPENDIX: Grid Support Utility Interactive Inverters

Appendix A: Rule 21

Details CA Rule 21 settings for voltage and frequency ride-through.

Appendix B: HECO

Provides HECO specific settings for ride-through capabilities.

Appendix C: Assembly Note

Offers assembly guidance and screw torque specifications for various models.

Delta M60U Specifications

General IconGeneral
AC Voltage [V]400
Output Power60 kVA
Frequency50 / 60 Hz
CategoryInverter
Output Voltage400 V
Protection FeaturesOvervoltage protection