Chapter 12 Descriptions of Parameter SettingsMS300
305
When Pr.02-09 is set to 0:
The increasing or decreasing Frequency command (F) operates according to the setting for
acceleration or deceleration time (refer to Pr.01-1201-19).
When Pr.02-09 is set to 1:
The increasing or decreasing Frequency command (F) operates according to the setting of
Pr.02-10 (0.001–1.000 Hz/ms).
When Pr.02-09 is set to 2:
The increasing / decreasing frequency command (F) operates according to the pulse of Pr.02-
10.