Chapter 13 Warning CodesMS300
484
ID No.
Display on LCD Keypad
Warning Name
Description
13
Under current
(uC)
Low current
Action and Reset
Action Condition
Pr.06-71
Action Time
Pr.06-72
Warning Setting Parameter
Pr.06-73
0: No function
1: Fault and coast to stop
2: Fault and ramp to stop by the 2
nd
deceleration time
3: Warn and continue operation
Reset Method
Auto
“Warningoccurs when Pr.06-73 = 3. The “Warningautomatically
clears when the output current is larger than (Pr.06-71+0.1 A).
Manual
“Erroroccurs when Pr.06-73 = 1 and 2. You must reset manually.
Reset Condition
Immediately reset
Record
Does not record when Pr.06-73 = 3 and uC displays (“Warning”).
Cause
Corrective Actions
Broken motor cable
Exclude the connection issue of the motor and its load.
Improper setting for the low
current protection
Set the proper settings for Pr.06-71, Pr.06-72 and Pr.06-73.
Low load
Check the loading status.
Make sure the loading matches the motor capacity.