EasyManuals Logo

Delta RPI-M20A User Manual

Delta RPI-M20A
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #135 background imageLoading...
Page #135 background image
5.2.7.4.5. Reacitve Power Control – cosφ (P)
此功能啟動後,變流器可隨著輸出之實功功率高低而饋入一定比例之虛
功功率。當國家設定為Italy LV或Italy MV時,使用者可進一步指定當
市電電壓高於V lock-in時方饋入虛功,電壓低於V lock-out後,無論此
時輸出實功功率為何,皆不饋入虛功。
a
b
c
d
Lock-out Voltage [ ]
Reactive Power Control
21. Jun 2010 13:50
Mode OFF[ ]
230.0
V
Lock-out Voltage
[ ]
Reactive Power Control
21. Jun 2010 13:50
Lower limit - cosφ
Upper limit - cosφ Cap 0.90
Ind 0.90
[
[
]
]
Lower Power 0[ ] %
Upper Power 100[ ] %
Lock-in Voltage 241.5[ ] V
Upper
Limit
Lower
Limit
P/Pn
1
cosφ
Lower
Power
Upper
Power
a
b
c
d
圖5-19 cosφ(P) 設定頁面
135
變流器開機

Table of Contents

Other manuals for Delta RPI-M20A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI-M20A and is the answer not in the manual?

Delta RPI-M20A Specifications

General IconGeneral
BrandDelta
ModelRPI-M20A
CategoryInverter
LanguageEnglish

Related product manuals