Chapter 5 Devices
5-25
Special
Item Description Attibutes Default
weight value that is set to output
H’A: OFF, when the weight is greater than the
Weight value that is set to output
D4564
Digital output modes
Y24 ~ Y27
H’0: digital output point (default)
H’1: ON, when there is no load on the load cell
H’2: OFF, when there is no load on the load cell
H’3: ON, when the weight is larger than the
specified maximum weight
H’4: OFF, when the weight is larger than the
specified maximum weight
H’5: ON, when the excitation voltage is
abnormal
H’6: OFFm when the excitation voltage is
abnormal F
H’7: ON, when the weight is in the specified
stability range
H’8: OFF, when the weight is in the specified
stability range
H’9: ON, when the weight is greater than the
weight value that is set to output
H’A: OFF, when the weight is greater than the
weight value that is set to output
R/W
◎
H’0
D4565 Weight changing display Default: K0; setting range: K0 ~ K32767 R/W
◎
K0
D4566 Status of Y point
Work with X and Y points
K0:Y point output enabled (default)
K1: Y point output closed
K2: Y point output on hold
R/W X K0
D4567
Y20 weight output setting
value (Low word)
When the weight is greater than the weight
value that is set to output, you can set the Y
point output to ON or OFF.
R/W
◎
K0
D4568
Y20 weight output setting
value (High word)
R/W
◎
K0
D4569
Y21 weight output setting
R/W
◎
K0
D4570
Y21 weight output setting
R/W
◎
K0
D4571
Y22 weight output setting
R/W
◎
K0
D4572
Y22 weight output setting
R/W
◎
K0
D4573
Y23 weight output setting
R/W
◎
K0
D4574
Y23 weight output setting
R/W
◎
K0
D4575
Y24 weight output setting
R/W
◎
K0