Chapter 5 Parameters_VFD-B Series 
Revision 10/2005, BE13, SW V4.08    5-39 
02 - 11 
aSource of the Auxiliary Frequency Command 
      Factory Setting: 00
  Settings  00  Digital keypad (PU01) UP/DOWN keys or Multi-function Inputs UP/DOWN. 
Last used frequency saved. 
    01  AVI  0 ~ +10VDC 
    02  ACI  4 ~ 20mA 
    03  AUI  -10 ~ +10VDC 
    04  RS-485 serial communication (RJ-11). Last used frequency saved. 
02 - 12 
aCombination of the Master and Auxiliary Frequency Command 
      Factory Setting: 00
  Settings  00  Master frequency + Auxiliary frequency 
    01  Master frequency - Auxiliary frequency 
These three parameters (Pr.02-10~02-12) are enabled when Pr.02-00 or Pr.02-13 are set to 06. If they are 
enabled, the frequency command will be determined by these parameters. 
 
02 - 02 
Stop Method 
        Factory Setting: 00
  Settings  00  STOP: ramp to stop  E.F.: coast to stop 
    01  STOP: coast to stop  E.F.: coast to stop 
    02  STOP: ramp to stop  E.F.: ramp to stop 
    03  STOP: coast to stop  E.F.: ramp to stop 
The parameter determines how the motor is stopped when the AC motor drive receives a valid stop 
command or detects External Fault. 
1. Ramp:  the AC motor drive decelerates to Minimum Output Frequency (Pr.01-05) according to the 
deceleration time and then stops. 
2. Coast:  the AC motor drive stops the output instantly upon command, and the motor free runs until it 
comes to a complete standstill. 
3. The motor stop method is usually determined by the characteristics of the motor load and how frequently 
it is stopped.