Chapter 4 Description of Parameters | VFD-VJ
4-32
Pressure Command
Control mode
VF FOCPG FOCPM
Factory setting: 0
Settings 0~400bar
Flow Command
Control mode
VF FOCPG FOCPM
Factory setting: 0
Settings 0~100%
When Pr.00-44 0, Pressure Command will not be given by the analog signal but input by Pr.00-44.
When Pr.00-45 0, Flow Command will not be given by the analog signal but input by Pr.00-45.
Pr00-44 & Pr.00-45 can be applied in an environment without input of analog signal to do simple test.
Pressure reference S1 time
Control mode
VF FOCPG FOCPM
Factory setting: 0
Settings 0~1000ms
Pressure reference S2 time
Control mode
VF FOCPG FOCPM
Factory setting: 0
Settings 0~1000ms
To increase the smoothness at start or stop while increasing or decreasing the percentage of the pressure
command. The longer the pressure reference time, the smoother it will be.
Flow reference S1 time
Control mode
VF FOCPG FOCPM
Factory setting: 0
Settings 0~1000ms
Flow reference S2 time
Control mode
VF FOCPG FOCPM
Factory setting: 0
Settings 0~1000ms
To increase the smoothness at start or stop while increasing or decreasing the percentage of the flow
command. The longer the flow reference time, the smoother it will be.