Appendix B: CANopen Overview | VFD-VJ   
 
Apx B - 8 
 
B-3-2 DS402 Standard Control Mode 
B-3-2-1 Related set up for an AC motor drive (following the DS402 standard) 
If you want to use the DS402 standard to control the motor drive, follow these steps: 
1.  Wire the hardware (refer to chapter B-2 Wiring for CANopen). 
2.  Set the operation source: set Pr.01-01 to 3 for CANopen communication card control.   
3.  Set the frequency source: set Pr.03-15 to 6. Choose the source for the Frequency command 
from the CANopen setting. 
4.  Set DS402 for the control mode: Pr.04-20=1 
5.  Set the CANopen station: set the CANopen station (range 1-127, 0 is the disable CANopen 
slave function) with Pr.04-17. Note: set Pr.00-02 = 7 to reset if the station number error 
CAdE or CANopen memory error CFrE appears. 
6.  Set the CANopen baud rate: set Pr.04-18 (CANBUS Baud Rate: 1M (0), 500K (1), 250K (2), 
125K (3), 100K (4) or 50K (5)). 
B-3-2-2 The status of the motor drive (by following DS402 standard) 
According to the DS402 definition, the motor drive is divided into 3 blocks and 9 statuses as 
described below. 
3 blocks 
1.  Power Disable: without PWM output 
2.  Power Enable: with PWM output 
3.  Fault: one or more errors have occurred. 
9 status 
1.  Start: power on 
2.  Not Ready to Switch On: the motor drive is initiating. 
3.  Switch On Disable: occurs when the motor drive finishes initiating.   
4.  Ready to Switch On: warming up before running. 
5.      Switch On: the motor drive has the PWM output, but the reference command is not       
effective. 
6.  Operate Enable: able to control normally. 
7.  Quick Stop Active: when there is a Quick Stop request, stop running the motor   
drive. 
8.  Fault Reaction Active: the motor drive detects conditions which might trigger error(s). 
9.  Fault: one or more errors have occurred in the motor drive.