Chapter 6. Suggestions and Error Corrections for Hybrid Servo DrivesC | VFD-VJ 
 
6-1
Chapter 6 Suggestions and Error 
Corrections for Hybrid Servo Drives 
 
6-1  Maintenance and Inspections 
6-2  Greasy Dirt Problem 
6-3  Fiber Dust Problem 
6-4 Erosion Problem 
6-5 Industrial Dust Problem 
6-6  Wiring and Installation Problem 
6-7 Multi-function Input/Output Terminals Problem 
6-8  Maintenance of Coupling 
The hybrid servo drive has a comprehensive fault diagnostic system that includes several different 
alarms and fault messages. Once a fault is detected, the corresponding protective functions will be 
activated. The following faults are displayed as shown on the hybrid servo drive digital keypad display. 
The six most recent faults can be read from the digital keypad or communication. 
The hybrid servo drive is made up by numerous components, such as electronic components, including 
IC, resistor, capacity, transistor, and cooling fan, relay, etc. These components can’t be used 
permanently. They have limited-life even under normal operation. Preventive maintenance is required to 
operate this hybrid servo drive in its optimal condition, and to ensure a long life. 
Check your hybrid servo drive regularly to ensure there are no abnormalities during operation and follows 
the precautions:   
 
  Wait 5 seconds after a fault has been cleared before performing reset via keypad of 
input terminal. 
  When the power is off after 5 minutes for ≦ 22kW models and 10 minutes for ≧ 
30kW models, please confirm that the capacitors have fully discharged by 
measuring the voltage between + and -. The voltage between + and - should be less 
than 25V
DC
. 
  Only qualified personnel can install, wire and maintain drives. Please take off any 
metal objects, such as watches and rings, before operation. And only insulated tools 
are allowed. 
  Never reassemble internal components or wiring. 
  Make sure that installation environment comply with regulations without abnormal 
noise, vibration and smell.