Chapter 4 Description of Parameters | VFD-VJ
4-31
I gain of Pressure overshoot 1
Control mode
VF FOCPG FOCPM
Factory setting: 0.2
Settings 0.00~500.00 sec.
Pressure overshoot level
Control mode
VF FOCPG FOCPM
Factory setting: 2
Settings 0~100%
By using the factory setting 250 bar of the Pr.00-08 Maximum Pressure Feedback, when the pressure is
over 5 bar (250*2%=5 bar), another integral time of Pr.00-39 will do overshoot protection.
When Pr.00-38=1 and Pr.00-39=0, Pr.00-42 is disabled.
Maximum Flow
Control mode
VF FOCPG FOCPM
Factory setting: 100
Settings 0~100%
Set up this parameter to adjust the maximum rotation frequency (maximum flow rate). It is not necessary to
stop the hybrid servo drive to set up this parameter. When this parameter is set to be 100%, it corresponds
to the maximum rotation frequency of Pr.01-02.