Chapter 5 Methods of Anomaly Diagnosis |V FD-VJ- 
 
 
5-20
5-2-3 Over Voltage (ov) 
OV: Over voltage
Yes
No
Yes
No
Lower voltage of power 
supply within the upper 
limit
Check if voltage of 
power supply is within 
the regulated range
It's likely hybrid servo 
controller breaks down or 
malfunctions due to noise. 
Please contact Delta for 
assistance.
If the voltage of DC BUS 
exceeds the protection value in 
action
Adjust the brake level 
and make sure it is higher 
than the local voltage 
Consider implementing
 brake unit
 
5-2-4 Low Voltage (Lv) 
Low voltage
Lv
No
Yes
Yes
No
No
No
Yes
No
Yes
No
Yes
If there is power outage (including 
momentary blackout)
Reset and 
restart
Any broken devices or 
bad connection in the 
supply circuit
Replace broken components 
and correct connection
Modify power supply system to 
comply with the regulations
Any load in the same power 
supply system that has larger 
load of starting current
If Lv occurs when the circuit 
breaker and electromagnetic 
contactor are ON
If the capacity of power supply 
transformer is appropriate
It's likely hybrid servo controller breaks 
down or malfunctions due to noise. 
Please contact Delta for assistance.
If voltage of power supply 
is within regulated range