APX A Optional Accessories | VFD-VJ
 
 
 
Apx A-8
A-3 Fuse 
 
  Fuse specifications smaller than the table below are allowed. 
  For installation in the United States, branch circuit protection must be provided in 
accordance with the National Electrical Code (NEC) and any applicable local codes. Use 
UL classified fuses to fulfill this requirement. 
  For installation in Canada, branch circuit protection must be provided in accordance with 
Canadian Electrical Code and any applicable provincial codes. Use UL classified fuses to 
fulfill this requirement.
 
 
Air Cooled 
230V model  Input Current (A) 
Line Fuse 
  Input Current (A)  Bussmann P/N 
VFD300VL23C-J 120  250  JJS-250 
VFD370VL23C-J 146  300  JJS-300 
 
Air Cooled: 
460V model  Input Current (A) 
Line Fuse 
 Input (A)  Bussmann P/N 
VFD110VL43C-J 24  50  JJS-50 
VFD150VL43C-J 30  60  JJS-60 
VFD185VL43C-J 37  80  JJS-80 
VFD220VL43C-J 47  100  JJS-100 
VFD300VL43C-J 60  125  JJS-125 
VFD370VL43C-J 73  150  JJS-150 
VFD450VL43C-J 91  200  JJS-200 
VFD550VL43C-J 110  225  JJS-225 
VFD750VL43C-J 150  300  JJS-300