Chapter 3. Machine Adjustment Procedure | VFD-VJ 
 
3-10
Induction motor 
  Set Pr.01-00 = 0 
Control mode 
Setting value   
of Pr. 01-00 
0: VF 
1: Reserved 
2: Reserved 
3: FOC vector control + Encoder (FOCPG) 
4: Reserved 
5: FOCPM 
6: Reserved 
  Set Pr.01-26 = 0 
Encode type 
Setting value   
of Pr.01-26 
0: ABZ 
1: ABZ+HALL (only used for Delta’s servo motors) 
2: ABZ+HALL 
3:Resolver 
  Set Pr.01-29 
Number of pulses for each revolution of the encoder 
Setting value   
of Pr.01-29 
1~20000 
  Set Pr. 01-08 
The rated current of the induction motor 
Setting value   
of Pr. 01-08 
0~655.35 Amps 
  Set Pr.01-09 
The rated power of the induction motor 
Setting value   
of Pr.01-09 
0.00 – 655.35kW 
  Set Pr.01-10 
The rated speed (rpm) of the induction motor 
Setting value   
of Pr.01-10 
0~65535 
  Set Pr.01-11 
Number of poles of the induction motor 
Setting value   
of Pr.01-11 
2~20 
  Check if the motor can be separated from the pump 
1.  If it can be separated, set Pr.01-07 as 1 and carry out a dynamic measurement 
2.  If it cannot be separated, open the safety valve, enter the no-load current of the induction 
motor Pr.01-12 and set Pr.01-07 as 2. Then carry out the static measurement